Monitor data parameters – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 94

94
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Chapter 2
Configure the XM-124 Standard Dynamic Measurement Module
Monitor Data Parameters
Table 12 - Monitor Data Parameters
Parameter Name
Description
Values/Comments
States whether a transducer fault exists on the associated channel.
If a fault exists, the overall and gap values may not be accurate.
Possible status values:
• No Fault
• Fault
Shows the measured average DC offset of the transducer signal. This
value is compared with DC High Limit and DC Low Limit to determine
whether the transducer is working properly.
Overall
Shows the measured standard overall value.
gSE Overall
Shows the measured gSE Overall value.
Band Pass
Shows the measured Band Pass Filter value.
Tracked Mag
Shows the measured Tracking Filter Magnitude value.
Tracked Phase
Shows the measured Tracking Filter Phase value.
Eccentricity
Shows the measured Eccentricity value.
Thrust Position
Shows the measured Thrust Position value.
Shows the measured sum harmonics value.
The tachometer must be enabled (Pulses Per
Revolution set to 1 or more), and a tachometer
signal must be present.
Band Measurement Status (XM Serial
Configuration Utility only)
States whether a fault condition exists on the associated channel. If a
fault exists, the band measurements may not be accurate.
Possible status values:
• No Fault
• Fault
Shows the measured band value.
Not 1X and Vector Status (XM Serial Configuration
Utility only)
States whether a fault condition exists on the associated channel. If a
fault exists, the not 1X and vector measurements may not be
accurate.
The following conditions can cause a fault:
• Atransducer fault on the associated channel
• No tachometer signal or a transducer fault exists on the
tachometer channel
• The machine speed changes too fast for the tracking algorithm to
keep up or if the frequency of FMAX goes outside the specified
criteria (see Sampling Mode on
page 68
)
Possible status values:
• No Fault
• Fault
Not 1X Value
Shows the magnitude of the vibration excluding the vibration at the
machine speed.
The tachometer must be enabled (Pulses Per
Revolution set to 1 or more), and a tachometer
signal must be present.
1X Magnitude
The magnitude of the vibration at the machine speed.
1X Phase
The phase of the vibration at the machine speed.
2X Magnitude
The magnitude of the vibration at two times the machine speed.
2X Phase
The phase of the vibration at two times the machine speed.
3X Magnitude
The magnitude of the vibration at three times the machine speed.
XM Configuration
Utility
EDS File
Transducer Fault
Transducer Status
XM Configuration
Utility
EDS File
DC Bias (Gap)
Measured DC Bias
XM Configuration
Utility
EDS File
Sum Harmonics
Sum Harmonics
Value
XM Configuration
Utility
EDS File
Band Measurement
Band Measured
Value