Services, Relay object (class id 323h), Relay object (class id 323 – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 142

142
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix B
CIP Objects
Services
(1)
Attributes can only be set while the device is in Program mode. See the description of the Device Mode Object for more information.
Relay Object (Class ID 323
H
)
The Relay Object models a relay (actual or virtual). A relay can be activated or
deactivated based on the status of one or more alarms.
7
Get
Time Constant
REAL
The detection time constant
associated with the output
smoothing filter (for the RMS and
DC meters) or the decay rate of the
peak meters.
This setting is based on the Low
Frequency Cutoff (Channel object) and
Measurement (attribute 6).
If Measurement is set to 3 or 4, the
Overall Time Constant is 1.5 seconds.
If Measurement is set to 0, 1, or 2, the
table below shows the Time Constant.
8
Get
Damping Factor
REAL
The damping factor associated
with output smoothing filter for
the RMS and DC meters (not used
with peak meters).
1.0
9
Get/Set
Overall Filter
USINT
Overall filter type applied to the
input signal before the
measurement is performed.
0 = None
1 = Low Pass Filter
2…255 Reserved
10
Get/Set
Low Pass Corner
Frequency
UINT
The corner frequency of the low
pass filter.
100…20,000 Hz
Table 63 - Overall Measurement Object Instance Attributes
Attr ID
Access Rule
Name
Data Type
Description
Semantics
Low
Frequency
Cutoff
Overall
Time
Constant
0.2 Hz
0.8
1 Hz
0.16
5 Hz
0.045
10 Hz
0.045
40 Hz
0.045
Table 64 - Overall Measurement Object Services
Service Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.