Install the XM-124 Standard Dynamic Measurement Module
connector cannot exceed 3 A. Refer to the specifications for the specific modules
for power requirements.
Figure 2 is an illustration of wiring modules using separate power connections.
Figure 2 - XM Modules with Separate Power Connections
Table 1 - Power Supply Requirements
ATTENTION: A separate power connection is necessary if the total current draw
of the interconnecting modules is greater than 3 A.
Any limited power
source that satisfies
the requirements
specified below
XM Power Supply Requirements
Protection
Listed Class 2 rated supply
Fused
(1)
ITE Listed SELF supply
Fused
(1)
ITE Listed PELV supply
Output Voltage
24V DC ± 10%
Output Power
100 W max (~4 A @ 24V DC)
Static Regulation
±2%
Dynamic Regulation
±3%
Ripple
<100 mV pp