Connect a passive transducer – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 37

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
37
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Figure 19 - Non-contact Sensor to Channel 2 Wiring
Connect a Passive Transducer
The figures below show the wiring of a passive transducer, such as a velocity
sensor, to the terminal base unit.
TYPICAL WIRING FOR NON- CONTACT SENSOR
TO XM-120/121 DYNAMI C MEASUREMENT MODULE C HANNEL 2
COM
SIG
-24
Channel 2 Input Signal
-24V DC
1
17
22
Signal Common
21
Jumper ing terminal 21 to
terminal 22 configures
CH 2 buffer for -24V to +9V
Isolated Sensor Driver
Shield
Shield
Fl oating
38
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 2
ATTENTION: You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the transducer.
Any convenient chassis terminal may be used (see
IMPORTANT
The module does not power the sensor. It measures only the input voltage.