Chapter 2
Configure the XM-124 Standard Dynamic Measurement Module
measurements. Click Spectrum/Waveform to open the Spectrum/Waveform
options dialog box.
In this field
Values are
Comments
Sampling Mode
Choose the sampling mode:
• Asynchronous
• Synchronous with tach
The sampling mode determines whether the signal is
synchronized with the tachometer signal and has several
effects on the resulting measurements.
Synchronous sampling requires a tachometer signal.
Sampling Mode (continued)
Frequency Type
The frequency units (Hz or CPM).
Enter the FMAX in these units.
Asynchronous Sampling
Synchronous Sampling
The waveform measurement is
time-based
The waveform measurement is
position-based.
The spectrum measurement is
frequency-based.
The spectrum measurement is
order-based and the Number of
Lines must be evenly divisible
by Frequency Maximum.
The Frequency Maximum must
be specified in Hz.
Frequency Maximum must be
specified in orders.