Gse measurement options – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 73

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
73
Configure the XM-124 Standard Dynamic Measurement Module
Chapter 2
gSE Measurement Options
The gSE Measurement options apply to the Alternating gSE and Continuous gSE
measurement modes. These settings affect the gSE Overall or gSE FFT
measurements.
In this field
Values are
Comments
Full Scale
The maximum signal level expected to be processed by the channel for
gSE measurements. This value is used to determine the programmable
gain settings across each stage of the channel’s analog signal processing
circuit.
The default value is 20 gSE.
High Pass Filter
Choose the high pass filter to apply to the gSE measurement.
• 200 Hz
• 500 Hz
• 1000 Hz
• 2000 Hz
• 5000 Hz
The high pass filter is useful in removing low frequency signal
components that could otherwise dominate the signal. The
high pass filter attenuates frequencies less than the selected
frequency. It allows, or passes, frequencies greater than the
selecteded frequency.
Frequency maximum
Enter the maximum frequency for the gSE spectrum, 10 to 5000 Hz.
The gSE spectrum always uses asynchronous sampling mode
and the FMAX is always in Hz.
Number of lines
Choose the number of lines (bins) in the gSE spectrum measurement:
• 100
• 200
• 400
• 800
• 1600
This determines the frequency resolution of the gSE
spectrum.