Module status (ms) indicators, Relay indicator, Network status (ns) indicator – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 112: Channel 1 and channel 2 status indicators

112
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix A
Status Indicators
Module Status (MS)
Indicators
The following table describes the Module Status indicators.
Relay Indicator
The following table describes the relay indicator.
Network Status (NS)
Indicator
The following table describes the network status indicator.
Channel 1 and Channel 2
Status Indicators
The following table describes the channel indicators.
State
Probable Cause
Off
No power applied to the module.
Alternating Red/Green
Module performing power-up self-test.
Flashing Red
• Application firmware is invalid or not loaded. Download firmware to the
module.
• Firmware download is currently in progress.
• The Node Address or Communication Rate DIP switches have been
changed and do not reflect the settings currently in use.
Solid Red
An unrecoverable fault has occurred. The module may need to be repaired or
replaced.
Flashing Green
Module operating in Program Mode,
not performing its monitoring
functions.
Solid Green
Module operating in Run Mode, performing its monitoring functions.
State
Probable Cause
Off
The relay is not activated.
Solid Red
The relay is activated.
State
Probable Cause
Off
Module is not online.
• Module is autobauding.
• No power applied to the module; look at Module Status indicator.
Flashing Red
One or more I/O connections are in the timed-out state.
Solid Red
Failed communication (duplicate MAC ID or bus-off).
Flashing Green
Module is online but no connections are currently established.
Solid Green
Module is online with connections currently established.
State
Probable Cause
Off
• Normal operation within alarm limits on the channel.
• No power applied to the module. Look at Module Status indicator.
Solid Yellow
An alarm associated with this channel is in Alert.
Solid Red
An alarm associated with this channel is in Danger.
Flashing Red
A transducer fault exists on the channel. The DC bias is outside the DC Low
and High Limits.