Instances, Instance attributes, Services – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 134: Alarm object (class id 31dh), Class attributes, Class attributes instances

134
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix B
CIP Objects
Instances
A module provides only a single instance (instance 1) of the Acknowledge
Handler Object. This instance is associated with instance 4 of the Connection
Object, the slave COS connection to a higher level master.
Instance Attributes
Services
Alarm Object (Class ID 31DH)
The Alarm Object mode is a two-stage (alert and danger levels) alarm.
Class Attributes
Instances
There are 16 instances of this object.
Table 51 - Acknowledge Handler Object Instance Attributes
Attr ID
Access Rule
Name
Data Type
Default Value
1
Get/Set
Acknowledge Timer
UINT
16 ms
2
Get/Set
Retry Limit
USINT
1
3
Get
COS Producing Connection
Instance
UINT
4
Table 52 - Acknowledge Handler Object Services
Service Code
Class/Instance Usage
Name
0E
h
Instance
Get_Attribute_Single
10
h
Instance
Set_Attribute_Single
Table 53 - Alarm Object Class Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics
1
Get
Revision
USINT
Version of the implemented
object.
2 (indicates that Threshold Multiplier is
a REAL instead of USINT)