Instance 199 - dynamic assembly – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 121

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
121
CIP Objects
Appendix B
Instance 199 - Dynamic Assembly
This Assembly instance can be created and configured with the XM Serial or
RSMACC Enterprise Online. Using the configuration software, you determine
the format of the data. This assembly instance can be selected to be sent in
response to an I/O Poll request from a Master.
The dynamic Assembly can include all of the measurement values included in
Assembly instance 101. In addition, the dynamic Assembly can include the
following configuration parameters.
133
empty
134
Channel 2 Measurement Mode
135
empty
136…139
Channel 1 gSE Overall measurement value
140…143
Channel 2 gSE Overall measurement value
144…147
Channel 1 Eccentricity measurement value
148…151
Channel 2 Eccentricity measurement value
152…155
Channel 1 Band Pass measurement value
156…159
Channel 2 Band Pass measurement value
160…163
Channel 1 Tracked Magnitude measurement value
164…167
Channel 1 Tracked Phase measurement value
168…171
Channel 2 Tracked Magnitude measurement value
172…175
Channel 2 Tracked Phase measurement value
Table 34 - Instance 101 Data Format (measurement values assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Table 35 - Instance 199 Component Mapping
EPATH (where ii = instance
number)
Class
Name
Class
Number
Instance
Number
Attribute
Name
Attribute
Number
Data
Type
21 1D 03 24 ii 30 04
Alarm
31D
h
1…16
Alarm Enable
4
BOOL
21 1D 03 24 ii 30 05
Alarm
31D
h
1…16
Type
5
USINT
21 1D 03 24 ii 30 07
Alarm
31D
h
1…16
Condition
7
USINT
21 1D 03 24 ii 30 08
Alarm
31D
h
1…16
Alert Threshold (High)
8
REAL
21 1D 03 24 ii 30 09
Alarm
31D
h
1…16
Danger Threshold (High)
9
REAL
21 1D 03 24 ii 30 0A
Alarm
31D
h
1…16
Alert Threshold Low
10
REAL
21 1D 03 24 ii 30 0B
Alarm
31D
h
1…16
Danger Threshold Low
11
REAL
21 1D 03 24 ii 30 0C
Alarm
31D
h
1…16
Hysteresis
12
REAL
21 1D 03 24 ii 30 0D
Alarm
31D
h
1…16
Threshold (Set Point)
Multiplier
13
REAL
21 1D 03 24 ii 30 0E
Alarm
31D
h
1…16
Start-up Period
14
UINT
21 1D 03 24 ii 30 0F
Alarm
31D
h
1…16
Speed Range Enable
15
BOOL
21 1D 03 24 ii 30 10
Alarm
31D
h
1…16
Speed Range High
16
REAL
21 1D 03 24 ii 30 11
Alarm
31D
h
1…16
Speed Range Low
17
REAL