Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
1
Terminals are internally connected and isolated from the chassis terminals.
20
Tachometer (-)
Tachometer transducer/signal return, TACH Buffer return
21
Buffer/Xducer Pwr (-)
Provides negative (-24 V to +9 V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) and 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external sensor (40 mA maximum
load)
22
Buffer Power 2 IN
Channel 2 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for negative biased
transducers
23
CAN_High
DeviceNet bus connection, high differential (white wire)
24
CAN_Low
DeviceNet bus connection, low differential (blue wire)
25
+24 V Out
Internally connected to 24 V In
1
(terminal 44)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal
26
DNet V (+)
DeviceNet bus power input, positive side (red wire)
27
DNet V (-)
DeviceNet bus power input, negative side (black wire)
28
24 V Common
1
Internally connected to 24 V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
29
4…20 mA 2 (+)
4…20 mA output
300 ohm maximum load
30
4…20 mA 2 (-)
31
Chassis
Connection to DIN rail ground spring or panel mounting hole
32
Chassis
Connection to DIN rail ground spring or panel mounting hole
33
Chassis
Connection to DIN rail ground spring or panel mounting hole
34
Chassis
Connection to DIN rail ground spring or panel mounting hole
35
Chassis
Connection to DIN rail ground spring or panel mounting hole
36
Chassis
Connection to DIN rail ground spring or panel mounting hole
37
Chassis
Connection to DIN rail ground spring or panel mounting hole
38
Chassis
Connection to DIN rail ground spring or panel mounting hole
39
SetPtMult
Switch input to activate Set Point Multiplication (active closed)
40
Switch RTN
Switch return, shared between SetPtMult and Reset Relay
41
Reset Relay
Switch input to reset internal relay (active closed)
42
Reserved
43
24 V Common
1
Internally DC-coupled to circuit ground
44
+24 V In
Connection to primary external +24 V power supply, positive side
45
24 V Common
1
Connection to external +24 V power supply, negative side (internally DC-coupled to circuit
ground)
46
Reserved
47
Relay Common
Relay Common contact
48
Relay N.O.
Relay Normally Open contact
49
Reserved
50
Reserved
51
Reserved
Table 2 - Terminal Block Assignments
No.
Name
Description