Chapter 1
Install the XM-124 Standard Dynamic Measurement Module
European Hazardous Location Approval
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wrist strap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
European Zone 2 Certification (The following applies when the product bears the Ex Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC
and has been found to comply with the Essential Health and Safety Requirements relating to the design and
construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to
this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-0, EN
60079-15, and EN 60079-11.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV
radiation.
WARNING: The following warnings apply to installations of the XM-124.
• This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
• This equipment shall be used within its specified ratings defined by Rockwell
Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.
• Secure any external connections that mate to this equipment by using screws,
sliding latches, threaded connectors, or other means provided with this
product.
• Do not disconnect equipment unless power has been removed or the area is
known to be nonhazardous.
• This equipment shall be mounted in an ATEX certified enclosure with a
minimum ingress protection rating of at least IP54 (as defined in IEC60529)
and used in an environment of not more than Pollution Degree 2 (as defined in
IEC 60664-1) when applied in Zone 2 environments. The enclosure must use a
tool removable cover or door.
• This equipment must be used only with ATEX certified Rockwell Automation
terminal bases.