Instance attributes, Status, Identity object status t – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 116: Instance attributes status

116
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix B
CIP Objects
Instance Attributes
Status
The Status is a 16 bit value. The following bits are implemented.
Table 24 - Identity Object Instance Attributes
Attr ID
Access
Name
Data Type
Default Value
1
Get
Vendor ID
UINT
1 = Allen-Bradley
2
Get
Device Type
UINT
109 (Specialty I/O)
3
Get
Product Code
UINT
73
4
Get Revision:
Major
Minor
STRUCT OF USINT
USINT
Value varies with each firmware version.
Value varies with each firmware version.
5
Get
Status
WORD
6
Get
Serial Number
UDINT
7
Get Product
Name
SHORT_
STRING
XM-124 standard dynamic measurement module
Table 25 - Identity Object Status
Bit
Name
Description
0
Owned
TRUE indicates that the module has an owner. More specifically, the Predefined Master/Slave Connection Set has
been allocated to a master.
1
Reserved, set to 0
2
Configured
This bit is set whenever a saved configuration is successfully loaded from nonvolatile memory. This bit is cleared
whenever the default configuration is restored or loaded.
3
Reserved, set to 0
4 …7
Extended Device Status
8
Minor Recoverable Fault
Set whenever there is a transducer or tachometer fault.
9
Minor Unrecoverable Fault
Not implemented
Self-testing or unknown
0
Firmware update in progress
1
At least one faulted I/O connection
2
No I/O connections established
3
At least one I/O connection in Run mode
6
At least one I/O connection, all in Run mode
7