Services, Devicenet object (class code 03h), Class attributes – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 117: Devicenet object (class code 03

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
117
CIP Objects
Appendix B
Services
DeviceNet Object
(Class Code 03
H
)
The DeviceNet Object is used to provide the configuration and status of a
physical attachment to DeviceNet.
Class Attributes
10
Major Recoverable Fault
Set when there is a major recoverable fault.
11
Major Unrecoverable Fault
Set when there is a Module Status fault (Module Status indicator is solid red).
12…15
Reserved, set to 0
Table 25 - Identity Object Status
Bit
Name
Description
Cause
Description
Resolution
The boot program
is running.
The main application is missing or corrupt .
Update or reinstall the module
firmware.
The Relay
Expansion
module has been
removed.
If an XM-441 Expansion Relay module is present at
power-up and if any of Relay instances 2 through 5 are
enabled, then a Major Recoverable Fault will be
indicated if the Relay Expansion module is removed.
Reinstall the missing Relay
Expansion module or disable the
expansion module relays in the
XM-124 configuration.
The 24 Volt power
monitor
measures out-of-
range.
The power supply voltage is less than approximately
19.2V or is greater than approximately 28.8V.
Adjust or replace the power
supply to insure its output is 24V
±10%.
In all cases the XM-124 will attempt to continue making measurements, monitoring alarms and managing its
relays regardless of the Major Fault Indication or its cause.
Table 26 - Identity Object Services
Service Code
Class/Instance Usage
Name
01
h
Instance
Get_Attributes_All
05
h
Instance
Reset
0E
h
Instance
Get_Attribute_Single
10
h
Instance
Set_Attribute_Single
Table 27 - DeviceNet Object Class Attributes
Attr ID
Access
Name
Data Type
Default Value
1
Get
Revision
UINT
2