Page 119: Instance 100 - alarm and relay status

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
119
CIP Objects
Appendix B
Instances
Instance Attributes
Assembly Instance Attribute Data Format
Instance 100 - Alarm and Relay Status
This assembly is sent using COS messaging when any of the Alarm or Relay
Status values change.
Table 31 - Assembly Object Instances
Instance
Name
Type
Description
100
Default COS Message
Input
Alarm and Relay Status values
101
Default Poll Response Message
Input
Measurement values
199
Alternate Dynamic Poll Response
Message
Input
User configurable measurement values
and configuration parameters
Table 32 - Assembly Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Value
1
Get
Number of Members in list
UINT
Only supported for Dynamic Assembly instance
2
Set
Member List
Array of STRUCT:
Only supported for Dynamic Assembly instance
Member Data Description
UINT
Size of member data value in bits
Member Path Size
UINT
Member Path
Packed EPATH
3
Get
Data
Defined in tables on
the following pages.
Table 33 - Instance 100 Data Format (alarm and relay status values assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Relay 1 Status
Set Point
Multiplier
Alarm 2 Status
Alarm 1 Status
1
Relay 2 Status
Channel 1
Transducer
Status
Alarm 4 Status
Alarm 3 Status
2
Relay 3 Status
Channel 2
Transducer
Status
Alarm 6 Status
Alarm 5 Status
3
Relay 4 Status
Tachometer
Transducer
Status
Alarm 8 Status
Alarm 7 Status
4
Relay 5 Status
0
Alarm 10 Status
Alarm 9 Status
5
0
0
Alarm 12 Status
Alarm 11 Status
6
0
0
Alarm 14 Status
Alarm 13 Status
7
0
0
Alarm 16 Status
Alarm 15 Status