Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 35

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
35
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Figure 16 - IEPE Accelerometer to Channel 1 Wiring
Figure 17 - IEPE Accelerometer to Channel 2 Wiring
TYPI CAL WIRI NG FOR IEPE ACCELEROMETER
TO XM-120/121DYNAMIC MEASUREM ENT MO DULE CHANNEL 1
Shield
Pin A - Si gn al
Pin B - Com mon
Cable shield not
conn ecte d at this end
0
16
6
Channel 1 Input Signal
Signal Common
5
37
Jumpering terminal 5
to terminal 6 configures
CH 1 buffer for -5V to +24V
TYPICAL WIRING FOR IEPE ACCELEROMETER
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 1
TYPICAL WIRING FOR IEPE ACCELEROMETER
TO XM-120/ 121 DYNAMIC MEASUREMENT MODUL E CHANNEL 2
Shi eld
Pin A - Signal
Pin B - Common
Cabl e shield not
conn ecte d at this end
1
17
6
Channel 1 Input Signal
Signal Common
38
Jumpering terminal 6 to
terminal 22 configures
CH 2 buffer for -5V to +24V
Channel 2 Input Signal
22
TYPICAL WIRING FOR IEPE ACCELEROMETER
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 2