(1)
The AlarmLimitMultiply output tag in RSLogix 5000 software can also set the Setpoint Multiplier switch. It does not overwrite this
service.
Table 41 - Discrete Input Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics
3
Get
Value
BOOL
Alarm Limit Multiplier
0 = Off
1 = On
199
Set
Backdoor Service
USINT
Setting this attribute is equivalent
to requesting the specified service.
Set to one of the following
values to perform the
specified service:
32
h
= Open
33
h
= Close
The virtual Setpoint
Multiplier switch can be
set with the
AlarmLimitMultiply output
tag in RSLogix 5000
software.
Table 42 - Discrete Input Object Services
Service Code
Class/Instance Usage
Name
Description
0E
h
Class/Instance
Get_Attribute_Single Returns the contents of the specified
attribute.
10
h
Instance
Set_Attribute_Single
Sets the contents of the specified
attribute.
32
h
Instance
Open
Opens the virtual Setpoint Multiplier
switch
(1)
.
33
h
Instance
Close
Closes the virtual Setpoint Multiplier
switch
(1)
.