Instance attributes – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 135

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
135
CIP Objects
Appendix B
Instance Attributes
Table 54 - Alarm Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics
3
Get
Alarm Status
3 BITS
The current status of the alarm.
0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
4
Get/Set
Alarm Enable
BOOL
Indicates whether this alarm
object is enabled.
0 = Disabled
1 = Enabled
5
Get
Type
USINT
Type of Alarm
0 = Magnitude
1 = Vector
6
Get
Threshold Units
USINT
Indicates whether the thresholds
and deadband value are specified
in units of measure. Not applicable
to vector alarms.
Set to 1
1 = Measurement units
7
Get/Set
AlarmCondition
USINT
Indicates on which side of the
threshold values the alarm and
danger conditions exist. Not
applicable to vector alarms.
0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range
8
Get/Set
AlarmHAlertLimit
REAL
The threshold value for the alert
state of the alarm. (For range
conditions, this is the greater
threshold value.)
9
Get/Set
AlarmHDangerLimit
REAL
The threshold value for the Danger
state of the alarm. (For range
conditions, this is the greater
threshold value).
10
Get/Set
AlarmLAlertLimit
REAL
The lesser threshold value for the
Alert state of the alarm with a
range condition type.
11
Get/Set
AlarmLDangerLimit
REAL
The lesser threshold value for the
Danger state of the alarm with a
range condition type.
12
Get/Set
AlarmDeadband
REAL
The amount on the safe side of a
threshold by which the value must
recover to clear the alarm.
13
Get/Set
AlarmLimitMultiply (Setpoint
Multiplier)
REAL
Indicates how the threshold must
be adjusted when the setpoint
multiplication function is invoked.
0 = Disable alarm
> 0 = Multiply the thresholds by the value
14
Get/Set
AlarmLimitMultiplyPeriod
UINT
The amount of time that the
Threshold (Setpoint) Multiplier is
applied after the start-up signal is
received.
Seconds
15
Get/Set
AlarmSpeedRangeEn
BOOL
Indicates whether this alarm is
enabled only within a certain
machine speed range.
0 = No speed range (alarm is always
enabled)
1 = Speed range (alarm only enabled
within speed range)
16
Get/Set
AlarmSpeedHLimit
REAL
Indicates the greater threshold of
the machine speed range for
which the alarm is enabled
(disabled at greater speeds).
CPM
(must be greater than
AlarmSpeedLLimit)