Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 146

146
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Appendix B
CIP Objects
7
Get/Set
Number of Spectrum
Lines
UDINT
Number of lines or bins in the
spectrum data.
100, 200, 400, 800, or 1600
8
Get/Set
Window Type
USINT
The window function to be
applied to the waveform data
prior to computing the spectrum.
0 = Rectangular
1 = Hamming
2 = Hanning
3 = Flat Top
4 = Kaiser Bessel
9
Get/Set
Period
REAL
The period of the waveform.
Seconds if Domain = 0.
Cycles if Domain = 1.
10
Get
Number of Waveform
Points
UDINT
Number of points in the waveform
data.
256, 512, 1024, 2048, or 4096
11
Get
Overlap
USINT
The percent overlap applied to the
waveform data sets used for
calculating the spectrum.
Only 0% supported.
12
Get/Set
Data Format
USINT
The format of the spectrum data.
0 = Complex data
1 = Magnitude data
13
Get
Average Type
USINT
The type of averaging performed.
0 = Asynchronous (spectrum)
1 = Synchronous (waveform)
Determined by the Synchronous
attribute of the Channel Object.
When set to Asynchronous, consecutive
spectrum measurements are averaged
together to produce the Spectrum data.
When set to synchronous, synchronized
waveforms are averaged together to
produce the Waveform data, and the
Spectrum data is produced from the
averaged waveform. A trigger source from
a tachometer, for example, is required to
obtain the synchronized waveforms.
14
Get/Set
Number of Averages
UINT
The number of individual data sets
to be incorporated into the
average calculation.
0 = Invalid
1 = No averaging
> 1 = Averaging
15
Get/Set
Storage Option
BYTE
Determines what must be stored
in response to a storage trigger
event.
1 = Store waveform
2 = Store spectrum
16
Get
Storage Timestamp
LTIME
Records the timestamp of the
stored data.
64-bit microsecond counter value.
Table 68 - Spectrum Waveform Measurement Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics