Cos message format, Xm status values – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 104

104
Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
Chapter 3
Operate the Module
COS Message Format
The XM-124 module’s COS message contains 8 bytes of data as defined in the
table below. The COS data can also be requested explicitly through Assembly
Object (Class ID 0x4), Instance 100 (0x64), Data Attribute (3).
XM Status Values
The following tables describe the XM Status values that are included in the COS
messages.
Table 17 - XM-124 COS Message Format
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Relay 1 Status
Setpoint Multiplier
Status
Alarm 2 Status
Alarm 1 Status
1
Relay 2 Status
Channel 1 Transducer
Status
Alarm 4 Status
Alarm 3 Status
2
Relay 3 Status
Channel 2 Transducer
Status
Alarm 6 Status
Alarm 5 Status
3
Relay 4 Status
Tachometer
Transducer Status
Alarm 8 Status
Alarm 7 Status
4
Relay 5 Status
Reserved
Alarm 10 Status
Alarm 9 Status
5
Reserved
Reserved
Alarm 12 Status
Alarm 11 Status
6
Reserved
Reserved
Alarm 14 Status
Alarm 13 Status
7
Reserved
Reserved
Alarm 16 Status
Alarm 15 Status
Table 18 - Alarm Status Descriptions
Alarm Status Value
Description
0
Normal
1
Alert
2
Danger
3
Disarm
4
Transducer Fault (Sensor OOR)
5
Module Fault
6
Tachometer Fault
7
Reserved
Table 19 - Setpoint Multiplier Status Descriptions
Setpoint Multiplier Status Value
Description
0
Not Activated
1
Activated