Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
shows the on-board relay connections for the modules.
Figure 11 - Relay Connection Wiring, Normally Closed and Normally Opened
TIP
The Expansion Relay module can be connected to the module to provide
additional relays. Refer the XM-441 Expansion Relay Module User Manual
for wiring details.
IMPORTANT
The NO terminal descriptions correspond to a de-energized (unpowered)
relay.
When the relay is configured for non-failsafe operation, the relay is
normally de-energized.
When the relay is configured for failsafe operation, the relay is normally
energized, and the behavior of the NO terminals is inverted.
Table 3 - Relay Connections for the XM-124 Module
Configured for
Failsafe Operation
Wire Contacts
Relay Terminals
Nonalarm
Alarm
Closed Opened
COM
47
NO
48
Configured for
Non-Failsafe Operation
Wire Contacts
Relay Terminals
Contact
Nonalarm
Alarm
Opened
Closed
COM
47
NO
48
+
–
Power
Source
Contact
COM NO
M
+
–
Power
Source
Contact
COM NO
32377 M