Chapter
1
Install the XM-124 Standard Dynamic
Measurement Module
This chapter discusses how to install and wire the XM-124 Standard Dynamic
Measurement Module (catalog number 1440-SDM02-01RA). It also describes
the module indicators and the basic operations of the module.
Topic
Page
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in
IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that
will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The enclosure must have suitable flame-retardant
properties to prevent or minimize the spread of flame, complying with a flame
spread rating of 5VA or be approved for the application if nonmetallic. The interior
of the enclosure must be accessible only by the use of a tool. Subsequent sections
of this publication may contain additional information regarding specific enclosure
type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publicat
,
for additional installation requirements
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of
protection provided by enclosures