Band Measurement
Object (Class ID 31E
H
)
The Band Measurement Object models the measurement of the amplitude of a
signal within a narrow frequency range.
Class Attributes
The Band Measurement Object provides no class attributes.
Instances
There are 10 instances of this object. Instances 1 through 8 are the Band
measurements that are derived from the spectrum data. Instances 9 and 10 are the
Band Pass measurements that are performed in Band Pass Filter measurement
mode.
17
Get/Set
AlarmSpeedLLimit
REAL
Indicates the lesser threshold of
the machine speed range for
which the alarm is enabled
(disabled at lesser speeds).
CPM
(Must be less than AlarmSpeedHLimit)
18
Get/Set
Name
STRING2
A name to help identify this alarm.
19
Get/Set
Measurement Identifier
EPATH
Identifies the measurement object
to which this alarm is applied.
See Parameter Object instances 10…25.
See
Table 48 on page 128
21
Get/Set
Detection Delay
UINT
The period that the measurement
must violate the threshold before
the Alert or Danger status is
indicated.
0…65,530 ms
Table 54 - Alarm Object Instance Attributes
Attr ID
Access Rule
Name Data
Type
Description
Semantics
Table 55 - Alarm Object Services
Service Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
(1)
Table 56 - Band Measurement Object Instances
Instance
Description
1
Channel 1 Band Measurement #1
2
Channel 2 Band Measurement #1
3
Channel 1 Band Measurement #2