Overall measurement object (class id 322h), Class attributes, Instances – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 141: Instance attributes, Class attributes instances instance attributes, Overall measurement object (class id 322

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
141
CIP Objects
Appendix B
Overall Measurement
Object (Class ID 322
H
)
The Overall Measurement Object models the measurement of the amplitude of a
signal including a wide frequency range.
Class Attributes
The Overall Measurement Object provides no class attributes.
Instances
There are two instances of this object.
Instance Attributes
16
h
Instance
Save
Validate the device configuration
settings if necessary and save them
to nonvolatile memory.
09
h
Instance
Delete
Delete the saved configuration from
nonvolatile memory.
15
h
Instance
Restore
Load the saved configuration or the
factory default configuration from
nonvolatile memory.
Table 62 - Device Mode Object Services
Service Code
Class/Instance Usage
Name
Description
Table 63 - Overall Measurement Object Instance Attributes
Attr ID
Access Rule
Name
Data Type
Description
Semantics
3
Get
Overall Value
REAL
Measured value
The output value of the measurement
performed by the Overall Measurement
Object on the input signal. The result of the
measurement process specified by
Measurement is converted to the units
specified by Data Units to produce the
Overall Value.
4
Get
Status
BOOL
Indicates if a fault or alarm has
occurred.
0 = Operating without alarms or faults.
1 = Alarm or fault condition exists. The
Overall Value attribute may not
represent the actual field value.
5
Get
Data Units
ENGUNIT
The units context of the Overall
Value attribute.
This setting is determined by the Channel
Object’s Output Data Units attribute (see
page 138
).
6
Get/Set
Measurement
USINT
The measurement (or calculation)
performed to produce the Overall
Value.
0 = RMS
1 = RMS peak
2 = RMS pk-to-pk
3 = Peak
4 = Peak-to-peak
5…255 Reserved