Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 33

9469370991 Rev A
27
DGC-2020HD
Table des registres par défaut
Nom
Description
Registre
Bit
Type Octets L/E
Plage
Mesure de puissance 3
PF retard
1004
1
Uint16 2
L
Faux = 0
Vrai = 1
27P-1
Blocage
1004
2
Uint16 2
L
Faux = 0
Vrai = 1
27P-1
Enclenchement
1004
3
Uint16 2
L
Faux = 0
Vrai = 1
27P-1
Déclenchement
1004
4
Uint16 2
L
Faux = 0
Vrai = 1
27P-1
Pré-alarme
1004
5
Uint16 2
L
Faux = 0
Vrai = 1
27P-1
Alarme
1004
6
Uint16 2
L
Faux = 0
Vrai = 1
27P-2
Blocage
1004
7
Uint16 2
L
Faux = 0
Vrai = 1
27P-2
Enclenchement
1004
8
Uint16 2
L
Faux = 0
Vrai = 1
27P-2
Déclenchement
1004
9
Uint16 2
L
Faux = 0
Vrai = 1
27P-2
Pré-alarme
1004
10
Uint16 2
L
Faux = 0
Vrai = 1
27P-2
Alarme
1004
11
Uint16 2
L
Faux = 0
Vrai = 1
27P-3
Blocage
1004
12
Uint16 2
L
Faux = 0
Vrai = 1
27P-3
Enclenchement
1004
13
Uint16 2
L
Faux = 0
Vrai = 1
27P-3
Déclenchement
1004
14
Uint16 2
L
Faux = 0
Vrai = 1
27P-3
Pré-alarme
1004
15
Uint16 2
L
Faux = 0
Vrai = 1
27P-3
Alarme
1005
0
Uint16 2
L
Faux = 0
Vrai = 1
27P-4
Blocage
1005
1
Uint16 2
L
Faux = 0
Vrai = 1
27P-4
Enclenchement
1005
2
Uint16 2
L
Faux = 0
Vrai = 1
27P-4
Déclenchement
1005
3
Uint16 2
L
Faux = 0
Vrai = 1
27P-4
Pré-alarme
1005
4
Uint16 2
L
Faux = 0
Vrai = 1
27P-4
Alarme
1005
5
Uint16 2
L
Faux = 0
Vrai = 1
27P-5
Blocage
1005
6
Uint16 2
L
Faux = 0
Vrai = 1
27P-5
Enclenchement
1005
7
Uint16 2
L
Faux = 0
Vrai = 1
27P-5
Déclenchement
1005
8
Uint16 2
L
Faux = 0
Vrai = 1
27P-5
Pré-alarme
1005
9
Uint16 2
L
Faux = 0
Vrai = 1
27P-5
Alarme
1005
10
Uint16 2
L
Faux = 0
Vrai = 1
27P-6
Blocage
1005
11
Uint16 2
L
Faux = 0
Vrai = 1
27P-6
Enclenchement
1005
12
Uint16 2
L
Faux = 0
Vrai = 1
27P-6
Déclenchement
1005
13
Uint16 2
L
Faux = 0
Vrai = 1
27P-6
Pré-alarme
1005
14
Uint16 2
L
Faux = 0
Vrai = 1
27P-6
Alarme
1005
15
Uint16 2
L
Faux = 0
Vrai = 1
59P-1
Blocage
1006
0
Uint16 2
L
Faux = 0
Vrai = 1
59P-1
Enclenchement
1006
1
Uint16 2
L
Faux = 0
Vrai = 1
59P-1
Déclenchement
1006
2
Uint16 2
L
Faux = 0
Vrai = 1
59P-1
Pré-alarme
1006
3
Uint16 2
L
Faux = 0
Vrai = 1
59P-1
Alarme
1006
4
Uint16 2
L
Faux = 0
Vrai = 1
59P-2
Blocage
1006
5
Uint16 2
L
Faux = 0
Vrai = 1
59P-2
Enclenchement
1006
6
Uint16 2
L
Faux = 0
Vrai = 1
59P-2
Déclenchement
1006
7
Uint16 2
L
Faux = 0
Vrai = 1