Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 300

294
9469370991 Rev A
Table des registres par défaut
DGC-2020HD
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
AEM 4 Entrée RTD 2 =
363
AEM 4 Entrée RTD 3 =
364
AEM 4 Entrée RTD 4 =
365
AEM 4 Entrée RTD 5 =
366
AEM 4 Entrée RTD 6 =
367
AEM 4 Entrée RTD 7 =
368
AEM 4 Entrée RTD 8 =
369
AEM 4 Entrée TC 1 =
370
AEM 4 Entrée TC 2 =
371
Sortie AVR = 372
Sortie GOV = 373
Sortie LS = 374
Protection configurable 8 Hystérésis
GG
25088
Float
4
L E Pourcentage 0 - 100
Protection configurable 8 Délai d’armement
GG
25090
Float
4
L E Seconde
0 - 300
Protection configurable 8 Seuil 1 - Type
GG
25092
Int32
4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
Protection configurable 8 Seuil 1 - Enclenchement
GG
25094
Float
4
L E s/o
-999 999 - 999 999
Protection configurable 8 Seuil 1 - Délai d'activation
GG
25096
Float
4
L E Seconde
0 - 300
Protection configurable 8 Seuil 1 - Configuration d'alarme
GG
25098
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
Protection configurable 8 Seuil 2 - Type
GG
25100
Int32
4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
Protection configurable 8 Seuil 2 - Enclenchement
GG
25108
Float
4
L E s/o
-999 999 - 999 999
Protection configurable 8 Seuil 2 - Délai d'activation
GG
25110
Float
4
L E Seconde
0 - 300
Protection configurable 8 Seuil 2 - Configuration d'alarme
GG
25112
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
Protection configurable 8 Seuil 3 - Type
GG
25114
Int32
4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
Protection configurable 8 Seuil 3 - Enclenchement
GG
25116
Float
4
L E s/o
-999 999 - 999 999
Protection configurable 8 Seuil 3 - Délai d'activation
GG
25118
Float
4
L E Seconde
0 - 300
Protection configurable 8 Seuil 3 - Configuration d'alarme
GG
25120
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
Protection configurable 8 Seuil 4 - Type
GG
25122
Int32
4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
Protection configurable 8 Seuil 4 - Enclenchement
GG
25124
Float
4
L E s/o
-999 999 - 999 999
Protection configurable 8 Seuil 4 - Délai d'activation
GG
25126
Float
4
L E Seconde
0 - 300
Protection configurable 8 Seuil 4 - Configuration d'alarme
GG
25128
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
Protection configurable 8 Courant d'échelonnage de ligne
basse
GG
25130
Float
4
L E s/o
0,001 - 3
Protection configurable 8 Tension d'échelonnage de ligne
basse
GG
25132
Float
4
L E s/o
0,001 - 3
Protection configurable 8 Désignation
GG
25134
String 16
L E s/o
0 - 16