Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation

Page 217

Advertising
background image

9469370991 Rev A

211

DGC-2020HD

Table des registres par défaut

Nom

Description

Groupe Registre Type Octets L/E

Unité

Plage

81-6

Mode

SG3

21812

Uint32 4

L E s/o

Désactivé = 0
Maximum = 1

Minimum = 2

81-6

Source

SG3

21814

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

81-6

Enclenchement

SG3

21816

Float

4

L E Hertz

37,5 - 66

81-6

Temporisation

SG3

21818

Float

4

L E Milliseconde 0 - 600 000

81-6

Inhibition de tension

SG3

21820

Float

4

L E Pourcentage 1 - 100

81-6

Configuration d’alarme

SG3

21822

Uint32 4

L E s/o

Statut uniquement = 0
Pré-alarme = 1

Alarme = 2

81-7

Mode

SG0

21824

Uint32 4

L E s/o

Désactivé = 0

Maximum = 1
Minimum = 2

81-7

Source

SG0

21826

Uint32 4

L E s/o

Alternateur = 0
Bus 1 = 1

Bus 2 = 2

81-7

Enclenchement

SG0

21828

Float

4

L E Hertz

37,5 - 66

81-7

Temporisation

SG0

21830

Float

4

L E Milliseconde 0 - 600 000

81-7

Inhibition de tension

SG0

21832

Float

4

L E Pourcentage 1 - 100

81-7

Configuration d’alarme

SG0

21834

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

81-7

Mode

SG1

21836

Uint32 4

L E s/o

Désactivé = 0
Maximum = 1

Minimum = 2

81-7

Source

SG1

21838

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

81-7

Enclenchement

SG1

21840

Float

4

L E Hertz

37.5 - 66

81-7

Temporisation

SG1

21842

Float

4

L E Milliseconde 0 - 600 000

81-7

Inhibition de tension

SG1

21844

Float

4

L E Pourcentage 1 - 100

81-7

Configuration d’alarme

SG1

21846

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

81-7

Mode

SG2

21848

Uint32 4

L E s/o

Désactivé = 0
Maximum = 1

Minimum = 2

81-7

Source

SG2

21850

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

81-7

Enclenchement

SG2

21852

Float

4

L E Hertz

37,5 - 66

81-7

Temporisation

SG2

21854

Float

4

L E Milliseconde 0 - 600 000

81-7

Inhibition de tension

SG2

21856

Float

4

L E Pourcentage 1 - 100

81-7

Configuration d’alarme

SG2

21858

Uint32 4

L E s/o

Statut uniquement = 0
Pré-alarme = 1

Alarme = 2

81-7

Mode

SG3

21860

Uint32 4

L E s/o

Désactivé = 0

Maximum = 1
Minimum = 2

81-7

Source

SG3

21862

Uint32 4

L E s/o

Alternateur = 0
Bus 1 = 1

Bus 2 = 2

81-7

Enclenchement

SG3

21864

Float

4

L E Hertz

37,5 - 66

81-7

Temporisation

SG3

21866

Float

4

L E Milliseconde 0 - 600 000

81-7

Inhibition de tension

SG3

21868

Float

4

L E Pourcentage 1 - 100

81-7

Configuration d’alarme

SG3

21870

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

81-8

Mode

SG0

21872

Uint32 4

L E s/o

Désactivé = 0

Maximum = 1

Minimum = 2

81-8

Source

SG0

21874

Uint32 4

L E s/o

Alternateur = 0
Bus 1 = 1

Bus 2 = 2

81-8

Enclenchement

SG0

21876

Float

4

L E Hertz

37,5 - 66

81-8

Temporisation

SG0

21878

Float

4

L E Milliseconde 0 - 600 000

81-8

Inhibition de tension

SG0

21880

Float

4

L E Pourcentage 1 - 100

81-8

Configuration d’alarme

SG0

21882

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

81-8

Mode

SG1

21884

Uint32 4

L E s/o

Désactivé = 0
Maximum = 1

Minimum = 2

81-8

Source

SG1

21886

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

81-8

Enclenchement

SG1

21888

Float

4

L E Hertz

37,5 - 66

Advertising