Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 217

9469370991 Rev A
211
DGC-2020HD
Table des registres par défaut
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
81-6
Mode
SG3
21812
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-6
Source
SG3
21814
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-6
Enclenchement
SG3
21816
Float
4
L E Hertz
37,5 - 66
81-6
Temporisation
SG3
21818
Float
4
L E Milliseconde 0 - 600 000
81-6
Inhibition de tension
SG3
21820
Float
4
L E Pourcentage 1 - 100
81-6
Configuration d’alarme
SG3
21822
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-7
Mode
SG0
21824
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-7
Source
SG0
21826
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-7
Enclenchement
SG0
21828
Float
4
L E Hertz
37,5 - 66
81-7
Temporisation
SG0
21830
Float
4
L E Milliseconde 0 - 600 000
81-7
Inhibition de tension
SG0
21832
Float
4
L E Pourcentage 1 - 100
81-7
Configuration d’alarme
SG0
21834
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-7
Mode
SG1
21836
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-7
Source
SG1
21838
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-7
Enclenchement
SG1
21840
Float
4
L E Hertz
37.5 - 66
81-7
Temporisation
SG1
21842
Float
4
L E Milliseconde 0 - 600 000
81-7
Inhibition de tension
SG1
21844
Float
4
L E Pourcentage 1 - 100
81-7
Configuration d’alarme
SG1
21846
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-7
Mode
SG2
21848
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-7
Source
SG2
21850
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-7
Enclenchement
SG2
21852
Float
4
L E Hertz
37,5 - 66
81-7
Temporisation
SG2
21854
Float
4
L E Milliseconde 0 - 600 000
81-7
Inhibition de tension
SG2
21856
Float
4
L E Pourcentage 1 - 100
81-7
Configuration d’alarme
SG2
21858
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-7
Mode
SG3
21860
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-7
Source
SG3
21862
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-7
Enclenchement
SG3
21864
Float
4
L E Hertz
37,5 - 66
81-7
Temporisation
SG3
21866
Float
4
L E Milliseconde 0 - 600 000
81-7
Inhibition de tension
SG3
21868
Float
4
L E Pourcentage 1 - 100
81-7
Configuration d’alarme
SG3
21870
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-8
Mode
SG0
21872
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-8
Source
SG0
21874
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-8
Enclenchement
SG0
21876
Float
4
L E Hertz
37,5 - 66
81-8
Temporisation
SG0
21878
Float
4
L E Milliseconde 0 - 600 000
81-8
Inhibition de tension
SG0
21880
Float
4
L E Pourcentage 1 - 100
81-8
Configuration d’alarme
SG0
21882
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
81-8
Mode
SG1
21884
Uint32 4
L E s/o
Désactivé = 0
Maximum = 1
Minimum = 2
81-8
Source
SG1
21886
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
81-8
Enclenchement
SG1
21888
Float
4
L E Hertz
37,5 - 66