Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 260

254
9469370991 Rev A
Table des registres par défaut
DGC-2020HD
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
51-6
Mode
SG0 1P 24320
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-6
Source
SG0 1P 24322
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-6
Enclenchement
SG0 1P 24324
Float
4
L E Ampère
0,9 - 20
51-6
Index de courbe
SG0 1P 24326
Uint32 4
L E s/o
S1 = 0
S2 = 1
L1 = 2
L2 = 3
D = 4
M = 5
I1 = 6
I2 = 7
V1 = 8
V2 = 9
E1 = 10
E2 = 11
A = 12
B = 13
C = 14
G = 15
F = 16
46 = 17
P = 18
51-6
Sens
SG0 1P 24328
Uint32 4
L E s/o
Entrant = 0
Sortant = 1
Non directionnel = 2
51-6
Utilisation de la réinitialisation
instantanée
SG0 1P 24330
Uint32 4
L E s/o
Intégrée = 0
Instantanée = 1
51-6
Constante TD
SG0 1P 24332
Float
4
L E s/o
0 - 9,9
51-6
Constante A
SG0 1P 24334
Float
4
L E s/o
0 - 600
51-6
Constante B
SG0 1P 24336
Float
4
L E s/o
0 - 25
51-6
Constante C
SG0 1P 24338
Float
4
L E s/o
0 - 1
51-6
Constante N
SG0 1P 24340
Float
4
L E s/o
0,5 - 2,5
51-6
Constante R
SG0 1P 24342
Float
4
L E s/o
0 - 30
51-6
Consigne de limitation en
fonction de la tension
SG0 1P 24344
Float
4
L E Volt
30 - 250
51-6
Mode de limitation en fonction
de la tension
SG0 1P 24346
Uint32 4
L E s/o
Désactivé = 0
Contrôle = 1
Limitation = 2
51-6
Configuration d’alarme
SG0 1P 24348
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
51-6
Échelonnage de ligne basse
SG0 1P 24350
Float
4
L E s/o
0,001 - 3
51-6
Source de limitation en fonction
de la tension
SG0 1P 24352
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-6
Constante Q
SG0 1P 24354
Float
4
L E s/o
0,1 - 10
51-6
Mode
SG0 3P 24356
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-6
Source
SG0 3P 24358
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-6
Enclenchement
SG0 3P 24360
Float
4
L E Ampère
0,9 - 20