Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 236

230
9469370991 Rev A
Table des registres par défaut
DGC-2020HD
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
51-2
Mode
SG0 1P 23168
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-2
Source
SG0 1P 23170
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-2
Enclenchement
SG0 1P 23172
Float
4
L E Ampère
0,9 - 20
51-2
Index de courbe
SG0 1P 23174
Uint32 4
L E s/o
S1 = 0
S2 = 1
L1 = 2
L2 = 3
D = 4
M = 5
I1 = 6
I2 = 7
V1 = 8
V2 = 9
E1 = 10
E2 = 11
A = 12
B = 13
C = 14
G = 15
F = 16
46 = 17
P = 18
51-2
Sens
SG0 1P 23176
Uint32 4
L E s/o
Entrant = 0
Sortant = 1
Non directionnel = 2
51-2
Utilisation de la réinitialisation
instantanée
SG0 1P 23178
Uint32 4
L E s/o
Intégrée = 0
Instantanée = 1
51-2
Constante TD
SG0 1P 23180
Float
4
L E s/o
0 - 9,9
51-2
Constante A
SG0 1P 23182
Float
4
L E s/o
0 - 600
51-2
Constante B
SG0 1P 23184
Float
4
L E s/o
0 - 25
51-2
Constante C
SG0 1P 23186
Float
4
L E s/o
0 - 1
51-2
Constante N
SG0 1P 23188
Float
4
L E s/o
0,5 - 2,5
51-2
Constante R
SG0 1P 23190
Float
4
L E s/o
0 - 30
51-2
Consigne de limitation en
fonction de la tension
SG0 1P 23192
Float
4
L E Volt
30 - 250
51-2
Mode de limitation en fonction
de la tension
SG0 1P 23194
Uint32 4
L E s/o
Désactivé = 0
Contrôle = 1
Limitation = 2
51-2
Configuration d’alarme
SG0 1P 23196
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
51-2
Échelonnage de ligne basse
SG0 1P 23198
Float
4
L E s/o
0,001 - 3
51-2
Source de limitation en fonction
de la tension
SG0 1P 23200
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-2
Constante Q
SG0 1P 23202
Float
4
L E s/o
0,1 - 10
51-2
Mode
SG0 3P 23204
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-2
Source
SG0 3P 23206
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-2
Enclenchement
SG0 3P 23208
Float
4
L E Ampère
0,9 - 20