Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 266

260
9469370991 Rev A
Table des registres par défaut
DGC-2020HD
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
78-1
Source
SG0
24610
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-1
Enclenchement
SG0
24612
Float
4
L E Degré
2 - 90
78-1
Configuration d’alarme
SG0
24614
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-1
Mode
SG1
24616
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-1
Source
SG1
24618
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-1
Enclenchement
SG1
24620
Float
4
L E Degré
2 - 90
78-1
Configuration d’alarme
SG1
24622
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-1
Mode
SG2
24624
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-1
Source
SG2
24626
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-1
Enclenchement
SG2
24628
Float
4
L E Degré
2 - 90
78-1
Configuration d’alarme
SG2
24630
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-1
Mode
SG3
24632
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-1
Source
SG3
24634
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-1
Enclenchement
SG3
24636
Float
4
L E Degré
2 - 90
78-1
Configuration d’alarme
SG3
24638
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-2
Mode
SG0
24640
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-2
Source
SG0
24642
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-2
Enclenchement
SG0
24644
Float
4
L E Degré
2 - 90
78-2
Configuration d’alarme
SG0
24646
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-2
Mode
SG1
24648
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-2
Source
SG1
24650
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-2
Enclenchement
SG1
24652
Float
4
L E Degré
2 - 90
78-2
Configuration d’alarme
SG1
24654
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-2
Mode
SG2
24656
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-2
Source
SG2
24658
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-2
Enclenchement
SG2
24660
Float
4
L E Degré
2 - 90
78-2
Configuration d’alarme
SG2
24662
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
78-2
Mode
SG3
24664
Uint32 4
L E s/o
Désactivé = 0
Activé = 1
78-2
Source
SG3
24666
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
78-2
Enclenchement
SG3
24668
Float
4
L E Degré
2 - 90
78-2
Configuration d’alarme
SG3
24670
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
Protection du voltage de
la batterie
Mode batterie faible
GG
24672
Uint32 4
L E s/o
Non = 0
Oui = 1
Protection du voltage de
la batterie
Mode sous-tension
GG
24674
Uint32 4
L E s/o
Non = 0
Oui = 1
Protection du voltage de
la batterie
Mode surtension
GG
24676
Uint32 4
L E s/o
Non = 0
Oui = 1
Protection du voltage de
la batterie
Seuil de batterie faible
GG
24678
Float
4
L E Volt
4 - 28