Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation
Page 263

9469370991 Rev A
257
DGC-2020HD
Table des registres par défaut
Nom
Description
Groupe Registre Type Octets L/E
Unité
Plage
51-6
Mode
SG2 1P 24464
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-6
Source
SG2 1P 24466
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-6
Enclenchement
SG2 1P 24468
Float
4
L E Ampère
0,9 - 20
51-6
Index de courbe
SG2 1P 24470
Uint32 4
L E s/o
S1 = 0
S2 = 1
L1 = 2
L2 = 3
D = 4
M = 5
I1 = 6
I2 = 7
V1 = 8
V2 = 9
E1 = 10
E2 = 11
A = 12
B = 13
C = 14
G = 15
F = 16
46 = 17
P = 18
51-6
Sens
SG2 1P 24472
Uint32 4
L E s/o
Entrant = 0
Sortant = 1
Non directionnel = 2
51-6
Utilisation de la réinitialisation
instantanée
SG2 1P 24474
Uint32 4
L E s/o
Intégrée = 0
Instantanée = 1
51-6
Constante TD
SG2 1P 24476
Float
4
L E s/o
0 - 9,9
51-6
Constante A
SG2 1P 24478
Float
4
L E s/o
0 - 600
51-6
Constante B
SG2 1P 24480
Float
4
L E s/o
0 - 25
51-6
Constante C
SG2 1P 24482
Float
4
L E s/o
0 - 1
51-6
Constante N
SG2 1P 24484
Float
4
L E s/o
0,5 - 2,5
51-6
Constante R
SG2 1P 24486
Float
4
L E s/o
0 - 30
51-6
Consigne de limitation en
fonction de la tension
SG2 1P 24488
Float
4
L E Volt
30 - 250
51-6
Mode de limitation en fonction
de la tension
SG2 1P 24490
Uint32 4
L E s/o
Désactivé = 0
Contrôle = 1
Limitation = 2
51-6
Configuration d’alarme
SG2 1P 24492
Uint32 4
L E s/o
Statut uniquement = 0
Pré-alarme = 1
Alarme = 2
51-6
Échelonnage de ligne basse
SG2 1P 24494
Float
4
L E s/o
0,001 - 3
51-6
Source de limitation en fonction
de la tension
SG2 1P 24496
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-6
Constante Q
SG2 1P 24498
Float
4
L E s/o
0,1 - 10
51-6
Mode
SG2 3P 24500
Uint32 4
L E s/o
Désactivé = 0
IA = 1
IB = 2
IC = 3
Imax = 4
3I0 = 5
I2 = 6
IG = 7
I1 = 8
51-6
Source
SG2 3P 24502
Uint32 4
L E s/o
Alternateur = 0
Bus 1 = 1
Bus 2 = 2
51-6
Enclenchement
SG2 3P 24504
Float
4
L E Ampère
0,9 - 20