Chapter 3 Configure XM Module in RSLogix 5000 Software
Nominal Sensitivity
Choose the sensitivity of the transducer.
Your choice controls the list of possible full
scale selections.
The default is 200.0 mV/mil (displacement).
Actual Sensitivity
Enter the sensitivity value of the transducer that is
included with the transducer’s calibration
documentation. Due to manufacturing variation, the
actual sensitivity may be different than the nominal
sensitivity.
This value is +/- 15% of the
value, see the above table.
Note: The nominal sensitivity is used if you
leave this field blank.
DC High Limit
Enter the maximum expected DC bias voltage from the
transducer.
Enter a value between -24...24 volts.
See
Approximate Expected Bias Voltage (V DC)
Table on page 65
Note: A voltage reading outside this range
constitutes a transducer fault, which is
indicated by the Channel LED flashing red and
the Ch0Fault or Ch1Fault input tag, depending
on the channel.
For information about the LEDs,
.
For information about the input tags,
see
.
DC Low Limit
Enter the minimum, or most negative, expected DC
voltage from the transducer.
In this field
Values are
Comments
Quantity of
Measure
Nominal
Sensitivity
Acceleration
10.0 mV/ g
25.0 mV/ g
50.0 mV/ g
100.0 mV/ g
500.0 mV/ g
1000.0 mV/ g
10000.0 mV/ g
Velocity
100.0 mV/ in/s
150.0 mV/ in/s
200.0 mV/ in/s
500.0 mV/ in/s
1000.0 mV/ in/s
4.0 mV/ mm/s
6.0 mV/ mm/s
8.0 mV/ mm/s
20.0 mV/ mm/s
40.0 mV/ mm/s
Displacement
100.0 mV/ mil
150.0 mV/ mil
200.0 mV/ mil
285.0 mV/ mil
3.94 mV/ µm
5.91 mV/ µm
7.87 mV/ µm
11.2 mV/ µm
Pressure
20.0 mV/ psi
50.0 mV/ psi
100.0 mV/ psi
0.29 mV/ mbar
0.73 mV/ mbar
1.45 mV/ mbar
Volts
1000.0 mV/V