Installing the XM Dynamic Measurement Module
Chapter 2
Power Up the Module
The module performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 second.
The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.
See Troubleshoot the Module on page 87
for more information about the
LED indicators.
Configure the Module
The module can be configured using the RSLogix™ 5000 software (Version
16.0 or later) Add-on Profile (AOP) and a 1440-ACNR ControlNet adapter.
See Configure XM Module in RSLogix 5000 Software on page 55
MS Indicator State
Description
Flashing Red and Green
Device self-test is in progress.
Solid Green or Flashing Green
Device self-test completed successfully,
and the firmware is valid and running.
Flashing Red
Device self-test completed, the hardware is
OK, but the firmware is invalid. Or, the
firmware download is in progress.
Solid Red
Unrecoverable fault, hardware failure, or
Boot Loader program may be corrupted.