Configure the connection properties – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 63

Publication ICM-UM002F-EN-E - March 2013
63
Configure XM Module in RSLogix 5000 Software
Chapter 3
Configure the Connection Properties
Use the Connection tab to modify the controller-to-module behavior.
1.
From the Module Properties dialog box, click the Connection tab.
2.
Enter the following information.
In this field
Values are
Comments
Requested Packet Interval
(RPI)
Enter a value between 20...640 ms, in 1 ms
increments. The default is 40 ms.
Specifies the period at which data updates
over a connection.
Note: If four updates are missed, the
connection closes and CommFault is set in the
input tag. (
See Input Data Type on page 92
).
Inhibit Module
Check to disable communication between the
controller and the module.
Clear to restore communication between the controller
and the module.
Major Fault on Controller if
Connection Fails While in
Run Mode
Check to have the controller produce a major fault if
the connection fails in Run mode.
Clear if the controller should not produce a major fault
if the connection fails in Run mode.
Module Fault
Displays the fault code returned from the
controller and the text detailing the Module
Fault. Click Help for additional information.