Page 148

148
Publication ICM-UM002F-EN-E - March 2013
Appendix B CIP Objects
6
Get/Set
Sensitivity Units ENGUNIT
Units of the denominator
of the
Sensitivity Value.
See DeviceNet Specification
Volume 1 Appendix K. Also see
Parameter Object instances 1
and 2 (
Valid values:
g = 1504
h
in/sec = 2B07
h
mil = 0800
h
psi = 1300
h
volt = 2D00
h
mm/s = 0900
h
µm = 2204
h
mbar = 1308
h
Pa = 1309
h
7
Get/Set
Fault High
REAL
The maximum expected
DC Bias voltage from the
transducer in volts.
Volts
A reading above this value
causes a transducer fault, which
is indicated by the Channel LED
flashing red.
8
Get/Set
Fault Low
REAL
The minimum expected
DC Bias voltage from the
transducer in volts.
Volts
9
Get/Set
Power Type
USINT
Indicates the type of
power supplied to the
transducer.
0 = Off
1 = IEPE (externally supplied)
2 = +24V (externally applied)
3 = -24V (externally applied from
terminal base)
4 = Bias Current (externally
supplied)
13
Get
DC Bias Time
Constant
REAL
The time constant value
used for exponential
averaging of the
DC Bias
value (a low pass
filter/output smoothing
filter).
1.769 seconds
Table B.49 Transducer Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Description
Semantics