CIP Objects
Appendix B
10
Get/Set
AlarmLAlertLimit
REAL
The lesser threshold value
for the Alert state of the
alarm with a range
condition type.
11
Get/Set
AlarmLDangerLimit
REAL
The lesser threshold value
for the Danger state of
the alarm with a range
condition type.
12
Get/Set
AlarmDeadband
REAL
The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.
13
Get/Set
AlarmLimitMultiply
(Setpoint Multiplier)
REAL
Indicates how the
threshold should be
adjusted when the
setpoint multiplication
function is invoked.
0 = Disable alarm
> 0 = Multiply the thresholds by
the value
14
Get/Set
AlarmLimitMultiplyPeriod
UINT
The amount of time that
the Threshold (Setpoint)
Multiplier is applied after
the startup signal is
received.
Seconds
15
Get/Set
AlarmSpeedRangeEn
BOOL
Indicates whether this
alarm is enabled only
within a certain machine
speed range.
0 = No speed range (alarm is
always enabled)
1 = Speed range (alarm only
enabled within speed range)
16
Get/Set
AlarmSpeedHLimit
REAL
Indicates the greater
threshold of the machine
speed range for which the
alarm is enabled (disabled
at greater speeds).
CPM
(must be greater than
AlarmSpeedLLimit)
17
Get/Set
AlarmSpeedLLimit
REAL
Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).
CPM
(Must be less than
AlarmSpeedHLimit)
18
Get/Set
Name
STRING2
A name to help identify
this alarm.
19
Get/Set
Measurement Identifier
EPATH
Identifies the
measurement object to
which this alarm is
applied.
See Parameter Object instances
10 to 25. See
Table B.24 Alarm Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type Description
Semantics