Status – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 105

Publication ICM-UM002F-EN-E - March 2013
105
CIP Objects
Appendix B
Status
The Status is a 16 bit value. The following bits are implemented.
Identity Object Status
Bit
Name
Description
0
Owned
TRUE indicates that the module has an owner. More
specifically, the Predefined Master/Slave Connection Set
has been allocated to a master.
1
Reserved, set to 0
2
Configured
This bit is set whenever a saved configuration is
successfully loaded from non-volatile memory. This bit is
cleared whenever the default configuration is restored or
loaded.
3
Reserved, set to 0
4 - 7
Boot Program
Vendor-specific, indicates that the boot program is
running. The Main Application must be corrupt or
missing. Use ControlFlash to reload the Main
Application.
8
Minor Recoverable
Fault
Set whenever there is a transducer or tachometer fault.
9
Minor Unrecoverable
Fault
Not implemented
10 Major
Recoverable
Fault
Set when there is a major recoverable fault.
11
Major Unrecoverable
Fault
Set when there is a module status fault (Module Status
LED is solid red).
12 - 15
Reserved, set to 0
ID_STATUS_SELF_TESTING
0x0000
ID_STATUS_NVS_UPDATE 0x0010
ID_STATUS_COMM_FAULT
0x0020
ID_STATUS_AWAIT_CONN
0x0030
ID_STATUS_CONNECTED
0X0060
ID_STATUS_IDLE
0X0070