Wiring, Maintenance, Specifications – Edwards Signaling Genesis WG4 Outdoor Horn-Strobe Manuel d'utilisation

Page 3

Advertising
background image

P/N 3102000-ML • REV 1.0 • ISS 11APR12

3 / 10

Figure 3: Jumper, switch, and protective cap locations

(1)

(6)

(3)

(5)

(2)

(4)

(1) Wire

slot

(2) JP3 horn volume jumper
(3) Protective cap

(4) JP4 strobe pattern jumper
(5) JP1 horn pattern jumper.
(6) S2 candela-setting switch

Wiring

See Figure 4. Connect all wiring in accordance with national
electrical codes and applicable local requirements.

Caution:

Equipment hazard. To avoid equipment damage,

ensure that the signal voltage does not exceed the voltage
rating of the device.

Figure 4: Wiring diagram

(4)

(5)

(6)

(1)

(2)

(3)

(1) Horn-strobe

in

(2) Horn-strobe in +
(3) Marking indicates the signal polarity

required to activate the device

(4) Horn-strobe out −
(5) Horn-strobe out +
(6) Not used

Figure 5: UL 1971 minimum light output (% of rating vs. angle)

100

95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10

5 0 5

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95

100

0

5 10 15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

-5

-10

-15

-20

-25

-30

-35

-40

-45

-50

-55

-60

-65

-70

-75

-80

-85

-90

(1) Angle
(2) Percentage of rated output

Note: Horizontal plot

Maintenance

Do not change the factory finish.

Perform a visual inspection and an operational test twice a
year, or as directed by the local authority having jurisdiction.

This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Specifications


Operating voltage
Horn-Strobe


24 VDC, 24 VFWR nominal

Dimensions (W × H × D)

5.6 Ч 8.5 Ч 1.4 in. (142 Ч 216 Ч 36 mm)

Sound level output

See Table 4, Table 5, Table 6, and
Table 7

Horn tone

3.2 kHz

Strobe operating current

See Table 11

Light output

See Table 8, Table 9, Table 10, and
Figure 5

Wire size

12 to 18 AWG (0.75 to 2.50 mm²)

Compatible electrical box
Outdoor
Indoor


Model 449
4 in. square by 1.5 in. deep box

Operating environment
Temperature
Relative

humidity


−40 to 151°F (−40 to 66°C)
0 to 95% noncondensing

Advertising