Wiring, Maintenance, Specifications – Edwards Signaling Genesis WG4 Outdoor Horn-Strobe Manuel d'utilisation
Page 3

P/N 3102000-ML • REV 1.0 • ISS 11APR12
3 / 10
Figure 3: Jumper, switch, and protective cap locations
(1)
(6)
(3)
(5)
(2)
(4)
(1) Wire
slot
(2) JP3 horn volume jumper
(3) Protective cap
(4) JP4 strobe pattern jumper
(5) JP1 horn pattern jumper.
(6) S2 candela-setting switch
Wiring
See Figure 4. Connect all wiring in accordance with national
electrical codes and applicable local requirements.
Caution:
Equipment hazard. To avoid equipment damage,
ensure that the signal voltage does not exceed the voltage
rating of the device.
Figure 4: Wiring diagram
(4)
(5)
(6)
(1)
(2)
(3)
(1) Horn-strobe
in
−
(2) Horn-strobe in +
(3) Marking indicates the signal polarity
required to activate the device
(4) Horn-strobe out −
(5) Horn-strobe out +
(6) Not used
Figure 5: UL 1971 minimum light output (% of rating vs. angle)
100
95 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10
5 0 5
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
100
0
5 10 15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
(1) Angle
(2) Percentage of rated output
Note: Horizontal plot
Maintenance
Do not change the factory finish.
Perform a visual inspection and an operational test twice a
year, or as directed by the local authority having jurisdiction.
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Specifications
Operating voltage
Horn-Strobe
24 VDC, 24 VFWR nominal
Dimensions (W × H × D)
5.6 Ч 8.5 Ч 1.4 in. (142 Ч 216 Ч 36 mm)
Sound level output
See Table 4, Table 5, Table 6, and
Table 7
Horn tone
3.2 kHz
Strobe operating current
See Table 11
Light output
See Table 8, Table 9, Table 10, and
Figure 5
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical box
Outdoor
Indoor
Model 449
4 in. square by 1.5 in. deep box
Operating environment
Temperature
Relative
humidity
−40 to 151°F (−40 to 66°C)
0 to 95% noncondensing