Edwards Signaling 1502 Manuel d'utilisation
Warning, Description, Installation

Installation Instructions for Floor Mount Electromagnetic Door Holders
Catalog Series 1501 and 1502
P/N 3100536 ISSUE 1 © 2003
501-152300-0-01
CHESHIRE, CT 203-699-3300
CUST. SERV. FAX
203-699-3365
TECH SERV. FAX
203-699-3078
Description
The 1501 Series is a floor mount door holder for use with single doors.
The 1502 Series is a floor mount door holder for use with double
doors. All are UL and cUL Listed and FM approved.
Table 1. Specifications
Cat. No.
Volts
Amps
1501-E1
12V DC
0.170
1501-E5
12V AC 60 Hz
0.150
1501-AQN5
24V AC 60 Hz
0.015
24V DC
0.015
120V AC 60 Hz
0.015
1502-E1
12V DC
0.170
1502-E5
12V AC 60 Hz
0.150
1502-AQN5
24V AC 60 Hz
0.015
24V DC
0.015
120V AC 60 Hz
0.015
2.
Install the cement anchors in the mounting holes. Remove the
cap from the conduit. Position the gasket and base plate on the
floor over the conduit.
3.
Place the gasket on the floor. Set the plate over the gasket with
the extruded bosses facing away from the gasket and secure
using (4) #1/4 x 20 x 1" screws (supplied). Install the conduit nut
on top of the plate.
Figure 1. Single Door Conduit Location
Figure 2. Double Door Conduit Location
Installation
Conduit Location
Install and wire in accordance with applicable codes, standards, such
as NFPA publications 70 (National Electrical Code), 72 (National Fire
Alarm Code), and 80 (Standard for Fire Doors and Fire Windows),
and/or other regulations applicable to the country and locality of
installation and in accordance with authorities having jurisdiction.
1.
Measure the door width. Calculate the radius (Figures 1 and 2)
by subtracting 5 5/8" from the door width.
2.
Single Door (Figure 1): Using the radius calculated in step 1,
draw an arc (using the pivot point of the door as the center point)
through the desired location of the door opening. Open the door
and draw a line through the arc 4 1/8" (105 mm) from the pull side
of the door.
Electromagnet Assembly Mounting
1.
Pull field wiring through conduit.
2.
Establish earth-ground continuity in accordance with applicable
codes, standards and authorities having jurisdiction.
3.
For -E1 and -E5 models, connect the field power wiring to the
electromagnet assembly wiring leads.
For -AQN5 models, refer to Figure 4 and connect as instructed
below:
a.
120V AC operation. Connect power field wiring to terminals
marked "120V AC" and "COM."
b. 24V AC/DC operation. Connect power field wiring to
terminals marked "24V AC/DC" and "COM."
c.
For, double door models, connect a jumper between
appropriate terminals on both terminal blocks and connect
field wiring to either terminal block.
WARNING
To prevent electrical shock, ensure power is disconnected.
NOTE: A 6" (152 mm) diameter clearance is required around the
conduit center for the door holder assembly.
3.
Double Door (Figure 2): Using the radius calculated in step 1,
draw an arc (using the pivot point of each door as the center
point) through the desired location of the door opening. Locate
the conduit where the two arcs intersect.
NOTE: Maximum door opening allowed is 130°.
4.
Install conduit.
NOTE: Maximum height of threaded conduit is 3/4" (19 mm)
above floor line. Maximum conduit size is 1/2" (13 mm).
Position the base plate so that the magnet lines up with
the contact plate on the door.
Floor Plate and Gasket Mounting
1.
Position the mounting base plate as a template, and mark the four
through holes. Remove the plate and drill holes 3/8" x 1 5/8"
(41 mm) deep in the floor. See Figure 3.
Figure 3. Dimensions
WALL
Pivot
Point
Radius
Conduit
location
5 5/8"
(143 mm)
4 1/8"
(105 mm)
130
o
Maximum
Door Opening
WALL
Pivot
Point
Radius
Radius
Conduit
location
5 5/8"
(143 mm)
130
o
Maximum
Door Opening
4 1/2"
(114 mm)
4 5/8"
(117 mm)
3 1/4"
(83 mm)
4 7/8"
(124 mm)
2" (51 mm) from
floor to center
2 3/8"
(60 mm)
3 1/4"
(83 mm)
(4) 5/16" (8 mm)
diameter holes for
mounting screws