Edwards Signaling 1502 Manuel d'utilisation
Page 2

4.
Mount the connected assembly onto the floor plate, and secure
it using (2) #1/4 x 20 x 1" screws (supplied).
Armature Assembly Mounting
NOTE: Armature assembly must be mounted vertically (Figure
5) to obtain correct alignment with the electromagnet.
120V AC 24V AC/
DC
COM
FRONT
VIEW
TOP
VIEW
Figure 4. Terminal Block
Figure 6. Thru-Bolt Mounting
Figure 7. Surface Concealed Mounting
Figure 5. Armature Mounting
P/N 3100536 ISSUE 1
501-152300-0-01
Mounting holes
Armature
(base view)
1.
Using a 5/32" Allen wrench, turn the contact plate adjusting screw
(Figures 6 and 7) counterclockwise to loosen the contact plate.
2.
Place the transfer marking points in the armature mounting holes
(Figure 5).
Mounting holes
Armature
(base view)
3.
To locate the two mounting holes in the door, hold the contact
plate centered against the magnet, open the door and press
against the transfer marking points on the armature base.
4.
Mount the armature assembly using one of the following methods:
a.
Thru-bolt mounting (Figure 6). Center punch the two holes
(at the points marked in step 3) and drill 5/16" diameter
through the door. Distance between the center points should
equal 1 3/4" (44 mm).
NOTE: Thru-bolt mounting is recommended for standard 1 3/4"
(44 mm) hollow metal, hollow core or composite type
wood doors.
Secure the armature assembly, with the contact plate adjust
screw facing up, to the door as shown in Figure 6 using
(2) #1/4-20 x 2" screws (supplied)
NOTE: For 2" doors, use (2) 1/4-20 x 2-1/4" bolts.
b. Surface concealed mounting (Figure 7). Measure two
points for 1/8" holes drilled 1/2" on center equidistant from
each marked point. Center punch the holes and drill 1/8"
diameter x 1 1/4" deep. Install the concealed mounting plate
using the two #10 x 1 1/2" screws provided.
NOTE: Surface concealed mounting is not recommended for
hollow metal, hollow core, or composite type wood
doors.
Align the holes for the concealed mounting plate in the
armature base with the pins on the concealed mounting plate.
Secure the armature assembly, with the contact plate adjust
screw facing up as shown in Figure 7, to the door by
tightening the set screw.
5.
Align the contact plate against the electromagnet. The contact
plate must be centered and lie flat against the magnet to ensure
sufficient holding force. Tighten the contact plate adjusting screw
until the plate is firm but not set. Do not overtighten the contact
plate.
6.
Recheck alignment and adjust if necessary.
7.
Adjust the door closer to exert 3 pounds of force when the door
is open and armature and magnet are in contact.
8.
Energize the electromagnet and check operation.
Holes for
concealed
mounting
plate
Armature
(base view)
2 Transfer points
PAGE 2
Lock edge
of door
2 3/8"
(60 mm)
5 5/8" (143 mm)
approx.
2"
(51 mm)
1 11/16"
(43 mm)
floor line
1 3/4"
(44 mm)
Door Plate
1 5/8"
(41 mm)
DOOR
(2) #1/4-20 x 2"
(51 mm)
screws provided
for a standard
1 3/4" (44 mm)
door
2" (51 mm) from floor to center
Contact plate
adjusting screw
Concealed
mounting
plate
1/2"
(13 mm)
Two #10 x 1 1/2"
(38 mm) screws
(supplied)
Set screw.
Tighten with 6/32" Allen wrench
to secure armature onto
mounting plate.
Door
Contact plate
Contact plate
adjusting screw
1/2" (13 mm)