Page 64

Gamatronic Electronic Industries Ltd.
56
POWER+ 3x208 V, User Guide, Release 2.1
#
Message
Explanation
16
BATFLT
Batteries failed last test
17
USER-1
User 1 input open
18
USER-2
User 2 input open
19
USER-3
User 3 input open
20
AC-BRN
Input ac supply Brown Out
21
ACIN_H
Ac input excessive
22
ACFAIL
Ac input failure
23
STSWCM
Static Switch does not respond
24
SLFFLT
Last controller self-test failed
25
BAT-CB
Battery Circuit Breaker Open
26
CURSHR
Current Sharing fault, load current is not equally divided between
modules
27
UPSOUT
Fault (no current) in 1 or more output stage
28
UPSHDN
UPS shutdown by EPO, Battery Discharge, ON/OFF pressed
29
OVLOAD
Load current is high
30
UPS-CM
One or more UPS’s not responding
31 STRTUP Startup
time-stamp
32 ------
N.A.
Each message is formatted as follows:
Time – HH:MM:SS
Date – YY:MM:DD
Data – dc voltage between + and – terminals for all events except LOADBP and
STSW status for LOADBP events. (See below.)
Even start (IN) and end (OUT)
Description – (See Table 3 on page 55)
Event number – 0 through 255, 255 being the most recent
Example:
11:23:56 05.01.28 436 IN -> E.P.O. 254
This message means that at 11:23:56 on January 28
th
2005, Emergency Power Off
alarm was registered as event 254; dc voltage at the time was 436 V being a sum of
(V+ -N) and (V- -N).