POWER+ 3x208 V, User Guide, Release 2.1
SETUP submenu Option 3: BATTERY
1> TEST-VOLTAGE
Set the battery test dc voltage (lowest)
2> TEST ALARM
Set the low battery dc voltage for alarm
3> CURRENT-LIMIT
1) Current Limit Value Setup
1> Set C. Limit Of Battery #1 (Value)
• Set the current limit for battery cabinet number one
2> Set C. Limit Of Battery #2 (Value)
• Set the current limit for battery cabinet number two
3> Set C. Limit Of Battery #3 (Value)
• Set the current limit for battery cabinet number three
2) Enable/Disable Current Limit (State)
• Enable or disable the battery current limit function
4> TEMP COMPENSAT..
1) Temperature Compensation Value Setup
• Set the temperature compensation value: 2.0 to 4.0 mV/C
O
per battery cell
2) Enable/Disable Temp. Compensation (State)
• Enable or disable the battery charging temperature compensation feature
3) Set ABSOLUTE Max & Min Voltages
1> Set ABSOLUTE MINimum Output Voltage
• Set the minimal dc voltage under compensation
2> Set ABSOLUTE MAXimum Output Voltage
• Set the maximal dc voltage under compensation
5) BATTERY TEST…
1> Activate Battery Test…
• Perform a manual battery test
2> Set Auto Battery Test Period
• Set a period between automatic battery tests in weeks
3> Set Auto Battery Test Top Time
• Set the longest time for the automatic battery test
6) CAPACITY (Value)
1> Set Capacity Of Battery #1 (Value)
• Set the capacity (AH) rating of the first battery bank
2> Set Capacity Of Battery #2 (Value)
• Set the capacity (AH) rating of the second battery bank
3> Set Capacity Of Battery #3 (Value)
• Set the capacity (AH) rating of the second battery bank
7) ‘AUTO’ TEST
• Perform a manual activation of the automatic battery test