5.2 Over-Voltage Protection
CAUTION!
To reduce the risk of fire, connect the UPS only to a circuit
provided with maximum branch circuit over-current protection
as indicated in
Table 1, in accordance with the National Electric
Code, NSI/NFPA 70.
ATTENTION !
Pour réduire le risque du feu, reliez L'UPS seulement à un circuit équipé de
protection maximum de surintensité de circuit de branche comme indiqué
au tableau 1, selon le code électrique national, au NSI/NFPA 70.
Ensure that the lines into and out of the UPS have protective circuit breakers
installed in accordance with the ratings listed in Table 1 for your Power+ model.
Table 1: Required over-current protection
POWER+
Model
Line
Maximum
over-current
protection
Ac input
Ac input bypass
Load
35 A
10 kVA
Battery dc input
30 A
Ac input
Ac input bypass
Load
70 A
20 kVA
Battery dc input
60 A
Ac input
Ac input bypass
Load
110 A
30 kVA
Battery dc input
90 A
Ac input
Ac input bypass
Load
150 A
40 kVA
Battery dc input
125 A
Ac input
Ac input bypass
50 kVA
Load
175 A