Gamatronic Electronic Industries Ltd.
POWER+ 3x208 V, User Guide, Release 2.1
47
8) ENABLE/DIS OPTIONS
1>
ENABLE/DISABLE
SHUTDOWN by long ac fail (On/Off)
• Enable or disable automatic shutdown after 3 hours of power failure
2> ENABLE/DISABLE Current Sensors
(On/Off)
• Enable or disable the usage of battery current sensors
3> ENABLE/DISABLE BATT Temperature sensor
(On/Off)
• Enable or disable the usage of battery temperature compensation
sensor
SETUP submenu Option 4: CHARGE
2> Floating Parameters Setup.
Set the actual dc voltage of the system (ups charging voltage)
SETUP submenu Option 5: TIME
● Set the date and the time of the RTC (real time clock) of the controller
SETUP submenu Option 6: SITE
● Set the 6 digit site number for identification through the management software
SETUP submenu Option 7: PASSWORD #1
● Set the 8 character password for entering the SETUP submenu
SETUP submenu Option 8: SERVICE
2> UPSs
Turn selected UPS modules on or off
4> DRYOUT TEST
Test the output dry contacts of the controller
5> CONFIGURE
1) # OF UPSs (redundancy)
• Set the number of modules used for redundancy only, which will not be
counted in the global power of the system
2) # OF UPSs (total)
• Set the number of UPS modules in the system
3) # Of BATT
• Set the number of battery cabinets for the system – 1, 2 or 3
4) Static Switch Setup
• Special function, not for customer use!
5) DRY, Alarms
1>
Dry1
Association
• Set the alarms that will trigger dry contact number 1
2>
Dry2
Association
• Set the alarms that will trigger dry contact number 2
3>
Dry3
Association
• Set the alarms that will trigger dry contact number 3