45
The “SETUP” submenu, option “7” from the main menu:
SETUP submenu Option 1: ALARM SET
1> AC VOLT
1) Set Ac High & Low Alarm Levels
• Set the ac low voltage and ac high voltage alarm levels
2) Set Ac Alarms Hysteresis
• Set the ac alarm response tolerance.
2> FLOAT VOLT
1)
BATEND
• Set the end of backup dc voltage
2)
BATLOW
• Set the battery low alarm voltage
4)
BAT-HI
• Set high dc voltage alarm
7> TEMPERATURE
1) Over Temperature
• Set the over-temperature alarm value
2) Under Temperature
• Set the under-temperature alarm value
9> INTEGRAT.
Set the number of communication repeats until processing an alarm
SETUP submenu Option 2: MODULE CONF.
1> NUM OF PHASE
Set the single/triple phase indication on the controller
2> MODULE/S FREQUENCY
Set the actual frequency for all modules – 50 Hz / 60 Hz or dip switch
hardware setting
3> MODULE/S VOLTAGE
Set the actual module output voltage: 110 V, 115 V, 120 V etc…
4> UPDATE VOLT/FREQ
Send the selected voltage and frequency values to UPS modules
5> OUTPUT ADJUST
Set the exact output voltage on each phase for each module
6> FREQUENCY LIMITS
Set the acceptable bypass frequency tolerance: 0.5 Hz to 4 Hz
7> DC CALIBRATION
Calibrate all modules to the measured battery voltage.