Self-test, History (logs), Figure – MaxPower Corp Gamatronic Power+ M100 Manuel d'utilisation
Page 62

Gamatronic Electronic Industries Ltd.
54
POWER+ 3x208 V, User Guide, Release 2.1
b a t T v o l T i - a c t i v E I - b u S
b a t T + : 2
1 6 V R 0 8 3 R 0 8 5
b a t T - : 2
1 6 V S 0 8 6 S 0 8 6
System
menu
Option 2
u p s : #
0 1 / 0 4 T 0 8 7 T 0 8 6
Figure 8-17: Battery voltages for module 1 of 4
Click Esc and then the Enter button again to return to the main menu (Figure
Self-Test
Main
menu
Option 3
From the main menu select option 3 (SELF TEST) to run a self-test of the
POWER+
. The self-test displays the window shown in Figure
run a self-test at any time without interfering in the normal operation of the
POWER+
. A self-test is also initiated by the POWER+ itself each day at
midnight.
The failure of a self-test sets on the self-test alarm. The self-test alarm can only
be cleared by a subsequent successful self test, or it can be cleared manually by
a maintenance technician. Powering the POWER+ down and up, for example,
does not clear the self-test alarm. This is because the failure of a self-test is
considered a serious event that should not be “forgotten”. A self-test failure is
also recorded in the alarm log.
Figure 8-18: Result screen from self-test
L O A D L
E V E L
G A M A T R O N I C - - - 1 1 : 2 0 : 2 5 - - -
R :
_ _ _ _ _ 0 3 0 A , 1 2 2 V B A T T E R Y : 4 3 2 V
S :
_ _ _ _ _ _ 0 2 4 A , 1 2 3 V U P S O K ( O N )
T :
_ _ _ _ _ _ _ 0 2
2
A , 1 2 2 V S T S W O K ( I N V )
History (Logs)
From the main menu select option 4 (HISTORY) to display the window shown in
Figure
8-19. The last 255 events reserved in the LOG are displayed, as shown in
Navigate the LOG by scrolling using the ▲ and ▼ keys.
T I M E D A T E V a l u e M E S S A G E #
1 6 : 1 4 : 5 6 0
5 . 0 1 . 0 3 4 3 6 . 0 V I N - > D C - - H V 2 5 4
1 6 : 1 4 : 5 8 0
5 . 0 1 . 0 3 4 3 5 . 0 V O U T > D C - - H V 2 5 5
Main
menu
Option 4
1 2 : 2 7 : 2 6 0
5 . 0 1 . 0 1 4 2 3 . O V I N - > U P S - C M 0 0 0
Figure 8-19: History logs
Navigate the LOG by scrolling using the ◄ and ► keys.
T I M E D A T E 1 2 3 4 5 6 7
8
#
1 6 : 1 4 : 5 6 0
5 . 0 1 . 0 3
2 5 4
1 6 : 1 4 : 5 8 0
5 . 0 1 . 0 3
2 5 5
Main
menu
Option 4
1 2 : 2 7 : 2 6 0
5 . 0 1 . 0 1
0 0 0
Figure 8-20: History log scroll
itemizes the log messages that appear on the controller panel.