Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse Manuel d'utilisation
Page 15

13
95-6526
14.2
AUCUNE CONNEXION
PAR L'UTILISATEUR
(CÂBLAGE USINE UNIQUEMENT)
1
2
3
4
5
6
7
8
9
10
11
12
13
B2057
CAL
SIGNAL
24 VDC –
SPARE
CAL
SIGNAL
24 VDC –
24 VDC +
24 VDC +
24 Vcc
+
–
COMMUTATEUR MAGNÉTIQUE
POUR CALIBRATION À DISTANCE
PAS DE
CONNEXION
MODÈLE PIRTB
ECLIPSE STANDARD
NOTE: SI NÉCESSAIRE, L'ALIMENTATION ET LA SORTIE 4-20 mA
PEUVENT ÊTRE PASSÉES PAR LE MODULE DE CALIBRATION
À DISTANCE VIA LE CÂBLAGE DU BLINDAGE.
24 Vcc –
24 Vcc –
24 Vcc +
24 Vcc +
CALIBRATION
+ 4-20 mA
– 4-20 mA
RS-485 A
RS-485 B
ALIMENTATION RELAIS
DÉRANGEMENT
ALARME BASSE
ALARME HAUTE
Figure 17—Module de Calibration à Distance Câblé pour l’Eclipse
A2567
CAL
SIGNAL
24 VDC –
SPARE
CAL
SIGNAL
24 VDC –
24 VDC +
24 VDC +
24 Vcc
+
–
COMMUTATEUR MAGNÉTIQUE
POUR CALIBRATION À DISTANCE
PAS DE
CONNEXION
24 Vcc –
24 Vcc –
24 Vcc +
24 Vcc +
BLINDAGE 24 Vcc
BLINDAGE 24 Vcc
COM 1 A
BLINDAGE COM 1
COM 1 B
COM 2 A
COM 2 B
BLINDAGE COM 2
CALIBRATION
1
2
3
4
5
6
7
8
9
10
11
12
13
ECLIPSE EQP
MODÈLE PIRTB
Figure 18—Module de Calibration à Distance Câblé sur PointWatch Eclipse Utilisé avec Système EQP