App.4-4 – Yokogawa 2-Wire Dual Channel Transmitter/Analyzer FLXA21 Manuel d'utilisation
Page 59

Annexe 4 Tableau de réglage utilisateur DO
App.4-4
IM 12A01A02-12F-E
Paramètre
Valeurs par
défaut
Valeurs applicables Réglages
utilisateur *Réf.
Display
setup
Dual
display
1st row
DO1
DO1, DO2, Calcu-
lated. Redundant
16.7.1
2nd row
DO2
DO1, DO2, Calcu-
lated. Redundant,
Empty
Individual
display
Main
display
DO1 (2)
1st line
Oxygen1 (2)
Oxygen1 (2),
Temperature1 (2)
2nd line
Temperature1 (2) Oxygen1 (2),
Temperature1 (2),
Empty
3rd line
Empty
Additional text
(blank)
(Max. 12 characters)
Trend
Trend
Graph
Screen:
1st Trend
Oxygen1 (2)
Oxygen1 (2),
Temperature1 (2),
(Calculated, Redun-
dant), Empty
16.7.2
2nd Trend
Temperature1 (2)
3rd Trend
Empty
X-axis:
Timing
Time Span (X)=
1 hour
15 min., 30 min., 1 hour,
2 hours, 4 hours, 8 hours,
24 hours, 7 days, 14 days
Y-axis:
Limits
Oxygen
low
0.00 mg/L, ppm
0.0 ppb, %SAT
mg/L, ppm:
0.00 à 50.00
ppb: 0.0 à 9999
%SAT: 0.0 à 600.0
high
20.00 mg/L, ppm
100.0 ppb, %SAT
Tempera-
ture
low
0.0 ºC
-20.0 à 150.0 ºC
high
50.0 ºC
Auto
Return
Auto Return
10min
Dissable, 10min,
60min
16.7.3
Adjust
contrast
Contrast:
0
-5 à +5
16.7.4
Calculated
data setup
Function
Differential
Differential, Average
16.8