Process Remote I/O (RIO) Communication Interface Module 11

Publication

1757-IN916C-EN-P - March 2008

Interpret the Status Indicators

The three status indicators on the module provide information about your
module and the status of communication with a host processor and with the
remote I/O network. The following tables outline the indicator condition and
the corresponding status for each indicator.

RIO Status Indicator – Remote Devices Status

The RIO indicator displays the status of the remote I/O network connection.

Error: Heard
Another RIO
Master

Another master has been detected on the network because of the
following possible reasons.

• The module is connected to a network with another RIO master.
• The module is connected to a Data Highway Plus network.

RIO Master
Config Scan

At startup, the module scans the RIO network to see what racks are
connected.

Rack xx I/O Grp
yy Size
Mismatch

The rack size in the stored configuration on the module for the rack at
rack number xx octal, starting I/O group yy, does not match the rack size
on the network.

Rack xx I/O Grp
yy Offline

The rack at rack number xx octal, starting I/O group yy, is not responding.

Firmware
Update

The firmware on the module is being updated.

Indicator

Status

Green

Successful communication with all configured racks.

Yellow

Idle, no racks are configured.

Red

One or more configured racks is not responding or a
protocol error has occurred within the last second.