Power supply indicator, Interpret the alphanumeric display – Rockwell Automation 1757-ABRIO Installation Instructions Manuel d'utilisation
Page 10

10 Process Remote I/O (RIO) Communication Interface Module
Publication
1757-IN916C-EN-P - March 2008
Power Supply Indicator
Interpret the Alphanumeric Display
The Process Remote I/O (RIO) Communication Interface Module displays
alphanumeric messages that provide diagnostic information about your
module. The warning messages display twice, then the normal display
resumes. The following table summarizes the messages.
Alphanumeric Display Message Descriptions
POWER Indicator
Power Supply Status
Recommended Action
Off
Not operating
• Turn power switch ON.
• Check power wiring
connections.
• Check fuse.
On
Operating
None, normal operation.
Message
Description
57ABRIO
Version x.xx.xx
The module’s firmware version, displayed at powerup. The three parts of
the version number are the major revision, the minor revision and the
build number.
Config
The module is being configured from the configuration program.
Inactive
The module is not receiving any messages that read or write tags. It is
scanning discrete I/O in program mode. Block transfers are not updating.
Active
The module is receiving messages that read or write tags. It is scanning
discrete I/O in run mode. Block transfers are updating.
Forced Active
The module has been put into active mode by the configuration program.
RIO Flash
Config Invalid
The configuration stored in Flash memory on the module is invalid due to
the following possible reasons.
• The module has never been configured.
• The module firmware has been updated and the configuration
format has changed.
• A fatal error has been captured.
To clear the invalid state, download the I/O configuration.