4.
Connect the signaling circuit field wires to the terminals
(Figures 2 and 3).Polarity must be observed for units operating
on 24 VDC.
5.
Mount horn assembly on the mounting plate (Figure 1).
a.
The inside of the top of the grille has hinges that pass
through cutouts and engage with tabs on the mounting
plate. With the bottom of the grille lifted out slightly,
place the grille over the mounting plate so that the hinges
of the grille are in the mounting cutouts.
b.
Properly seat the grille by pressing the bottom in.
c.
Fasten the bottom of the grille to the mounting plate by
installing the captive combination drive screw.
6.
Apply power and activate the horn unit to verify that it is
operating properly.
Maintenance
CAUTION
Should the unit fail to operate properly, do not attempt
repair. Contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year.
Figure 2. Wiring Diagrams
Figure 3. Terminal Block
Table 2. Specifications
P-047550-1785 ISSUE 2
N5 Model
AQ Model
Operating Voltage*
120V AC 50/60 Hz
24V AC 50/60 Hz
24V DC
Operating Current
24 mA
72 mA
22 mA
Sound Level Output at
10 feet (3.05 m)
Anechoic Chamber
96 dBA
Operating Environment
Indoor
93% @ 104F (40C) relative humidity; 32 to 120F (0 to
49C) variable ambient temperature
Outdoor
98% @ 104F (40C) relative humidity; 31 to 150F (-35 to
66C) variable ambient temperature
*The operating voltage to the horn may be continuous or coded such as march time or a
temporal pattern meeting ISO8201 (ANSI S3.41) Audible Emergency Evacuation Signal.